France

HyFive Tower

France – La Défense

Temperate Existing Building

Organisation : Icade - Esset Property Management

19.6 %
annual energy
savings achieved
Level : Silver

Energy performance

19.6 %
Energy savings
84.2 kWh/m²/year
Absolute performance
1.7 kgCO₂/m²/year
Carbon intensity

Key measures implemented

The main actions implemented to reduce the energy consumption of this building.

Efficiency Investments

Progressive replacement of the building management systems (BMS) installed in 1998.

Technical Optimization

Adjustment of heating and cooling controls: no heating or cooling production when outdoor temperatures are between 16°C and 21°C; adjustment of the control thresholds from +3°C/−3°C to +2°C/−2°C.
Optimisation of the water loop to recover heat from the more exposed façades, alongside optimisation of the water temperature control curve.
Optimisation of chilled water production and storage: storage at night and release in the morning.
Optimisation of water treatment.

Use Sufficiency

Engagement of building teams—including security, fire safety, technical maintenance and cleaning—in energy-saving initiatives.
Engagement of occupants through internal challenges between tenants.

Technical context

Floor area 33,300 m²
Activity type Office
Year built 1980 - 2000
Building structure status Property manager

Consumption data

Measurement periods

Reference period
Jan 2022 - Jan 2023
Monitoring period
Feb 2023 - Feb 2024

Annual Energy Impact